Motor
output(kw)
Inverter model
(N50 Series)
Wiring
Power lines Signal lines
Applicable equipment
Fuse(class H) rated 600V
0.75
1.5
2.2
E-100-022S
10A
15A
20A
0.14
§
¡
0.75
§
shielded
wire
1.25
§
2.0
§
E-100-007S
E-100-015S
Name
Function
R
T
U V W
P
RB
Thermal
relay
T1 T2 T3
L1 L2
Inverter
Standard Apparatus(3-phase input reference)
Option
Electroma-
gnetic contact
Fuse
Motor
Power supply
<Note>
Field wiring connection must be made by a UL listed and CSA certified, closed-loop
terminal connector sized for the wire gauge involved. Connector must be fixed using
the crimp tool specified by the connector manufacturer.
Be sure to consider the capacity of the circuit breaker to be used.
Be sure to use bigger wires for power lines if the distance exceeds 20m.
2
Use 0.75mm wire for the alarm signal wire.
Input-side AC reactor
for harmonic
suppression/power
coordination/power
improvement
EMI filter
Output-side noise
filter
AC reactor for
vibration
reduction/thermal
relay malfunction
prevention
This is useful when harmonic suppression measures must be
taken. when the main power voltage unbalance rate exceeds
3% and the main power capacity exceeds 500kVA, or when
a sudden power voltage variation occurs. It also helps to
improve the power factor.
Reduces the conductive noise on the main power wires
generated from the main power supply. Connect to the
inverter primary side(input side).
This is installed between the inverter and the motor to reduce
noise radiated from the main the control power wiring. It is
useful for reducing radio-wave disturbance in a radio or TV
set and for preventing malfunction of measuring instruments
or sensors.
Vibration may increases when driving a general-purpose
motor with an inverter as compared with operation on
commercial power. Connecting this reactor between the
inverter and the motor allows reduction of motor pulsation.
When the wirung between the inverter and the motor is 10m
or more, inserting the reactor prevents thermal relay malfun-
ction caused by harmonics resulting from incerter switching.
A current sensor can be used instead of the thermal relay
6-7