Section 6 • Alarms and Trips
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
IO Comm.:
Below message will be displayed on Main Screen when there is problem in Serial Modbus Communication be
-
tween IO Boards & MicroVission SBC Board.
I/O Comm Trip
Problem found in Com-
munication between SBC
& IO Boards
Low Oil Level:
Below messages will be displayed on Main Screen if Low Oil Level Digital Input is found Active Low.
Low Oil Level Trip will be only active when “Oil Level Trip” checkbox is enabled in Configuration screen.
Low Oil Level Warning
Low Oil Level Inhibit
Low Oil Level Alarm
Low Oil Level Trip
Low Oil Level Digital Input
is Active Low
Low Oil Level Digital Input is Active
Low
Low Oil Level Digital
Input is Active Low >=
Low Oil Level Alarm
Delay Time
Low Oil Level Digital Input
is Active Low >= Low Oil
Level Trip Delay Time
Low Discharge Pressure:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge Pressure
value from Measuring Instrument. There is no user configured setpoint.
Low Discharge Pressure
Warning
Low Discharge Pressure Inhibit
Low Discharge Pressure
Trip
Discharge Pressure <=
-66.5 Psig
Discharge Pressure <= -66.5 Psig
Discharge Pressure <=
-66.5 Psig
Low Discharge Temperature:
Below Messages will be displayed on Main Screen when there is a failure while reading Discharge Temperature
value from Measuring Instrument. There is no user configured setpoint.
Low Discharge Tempera-
ture Warning
Low Discharge Temperature Inhibit
Low Discharge Tempera-
ture Trip
Discharge Temperature <=
-100 °F
Discharge Temperature <= -100 °F
Discharge Temperature
<= -100 °F