B - 12
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-15. Alarms/Trips Block (Page 1)
Ethernet IP
Address
Modbus
Address
Alarms/Trips (Page 1)
Data Type Value
Mode
Lower
Range
Higher
Range
N61:0
40400
Low Suction Pressure Alarm
Setpoint #1
F-INT
Read-
Write
-15
300
N61:1
40401
Low Suction Pressure Trip Set
-
point #1
F-INT
Read-
Write
-15
300
N61:2
40402 High Discharge Pressure Alarm
Setpoint #1
F-INT
Read
N61:3
40403 High Discharge Pressure Trip
Setpoint #1
F-INT
Read
N61:4
40404 Low Process Temperature
Alarm Setpoint #1
F-INT
Read-
Write
-100
210
N61:5
40405 Low Process Temperature Trip
Setpoint #1
F-INT
Read-
Write
-100
210
N61:6
40406 High Process Temperature
Alarm Setpoint #1
F-INT
Read-
Write
-100
210
N61:7
40407
Low Suction Pressure Alarm
Setpoint #2
F-INT
Read-
Write
-15
300
N61:8
40408
Low Suction Pressure Trip Set
-
point #2
F-INT
Read-
Write
-15
300
N61:9
40409 High Discharge Pressure Alarm
Setpoint #2
F-INT
Read
N61:10
40410 High Discharge Pressure Trip
Setpoint #2
F-INT
Read
N61:11
40411 Low Process Temperature
Alarm Setpoint #2
F-INT
Read-
Write
-100
210
N61:12
40412 Low Process Temperature Trip
Setpoint #2
F-INT
Read-
Write
-100
210
N61:13
40413 High Process Temperature
Alarm Setpoint #2
F-INT
Read-
Write
-100
210
N61:14
40414 Low Process Pressure Alarm
Setpoint #1
F-INT
(Currently
Unused)
Read-
Write
-15
300
N61:15
40415 Low Process Pressure Trip Set-
point #1
F-INT
(Currently
Unused)
Read-
Write
-15
300
N61:16
40416 High Process Pressure Alarm
Setpoint #1
F-INT
(Currently
Unused)
Read-
Write
-15
350