6 – 5
Section 6 • Alarms and Trips
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
High Process Temperature:
Below Messages will be displayed on Main Screen when Process Temperature value rises below configured
setpoints. Refer Figure 6- 1 for Alarm setpoints.
There are two different set of Alarm setpoints which will be active depending on Active Control Mode selected
from Compressor Control screen.
These safeties will be only active when Active Control Mode selected from Compressor Control is “Process Tem
-
perature SP1” or “Process Temperature SP2”.
High Process
Temperature Alarm
Process Tempera-
ture >= High Process
Temperature Alarm
Setpoint 1 / Setpoint 2
Low Suction Temperature:
Below Messages will be displayed on Main Screen when Suction Temperature value drops below configured
setpoints. Refer Figure 6- 2 for Alarm & Trip setpoints.
Low Suction Temperature
Warning
Low Suction Temperature Inhibit Low Suction Tempera
-
ture Alarm
Low Suction Temperature
Trip
Suction Temperature <=
Low Suction Temperature
Alarm Setpoint
Suction Temperature <= Low Suc
-
tion Temperature Alarm Setpoint
Suction Tempera
-
ture <= Low Suction
Temperature Alarm
Setpoint
Suction Temperature <=
Low Suction Temperature
Trip Setpoint
High Discharge Temperature:
Below Messages will be displayed on Main Screen when Discharge Temperature value rises above configured
setpoints. Refer Figure 6- 2 for Alarm & Trip setpoints.
High Discharge Temperature Alarm & High Discharge Temperature Trip safeties will be monitored only once
High Discharge Temp Bypass Timer is lapsed.
High Discharge
Temperature Warning High Discharge Temperature Inhibit
High Discharge
Temperature Alarm
High Discharge
Temperature Trip
Discharge Temperature >=
High Discharge Tempera-
ture Alarm Setpoint
Discharge Temperature >= High Dis
-
charge Temperature Alarm Setpoint
Discharge Tempera-
ture >= High Discharge
Temperature Alarm
Setpoint
Discharge Temperature
>= High Discharge Tem
-
perature Trip Setpoint