6 – 10
Section 6 • Alarms and Trips
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
High Level Shutdown:
Below messages will be displayed when power is removed from the input module.
High Level Shutdown switch is wired to the digital input normally closed. Usually connected to a float switch on
a vessel containing liquid refrigerant. In case of multiple switches, any open switch will generate a relevant mes
-
sage depending on compressor operating mode.
When “Idle Time Trip” checkbox is enabled in Configuration screen, High Level Shutdown Trip will be monitored
even when compressor is idle.
High Level Shutdown
Warning
High Level Shutdown Inhibit
High Level Shutdown Trip
High Level Shutdown Digi-
tal Input is Active Low
High Level Shutdown Digital Input
is Active Low during Compressor
Start
High Level Shutdown
Digital Input is Active
Low while Compressor is
Running
Starter:
Below message will be displayed on Main Screen when Motor Auxiliary Contact Fails to Open after Compressor
shutdown.
Starter Shutdown Trip
Motor Auxiliary Contact is
Closed after Compressor
is Stopped
False Start:
Below message will be displayed on Main screen in following cases when Compressor is Idle.
1)
Motor Auxiliary Contact is Closed.
2)
Measured Motor Current Value is greater than Maximum Load Rating in Amperes.
False Start
Motor Auxiliary Contact is
Closed
OR
Motor Amperage > 20 %
Maximum Amps