B - 17
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-21. Configuration (Other) Block (continued)
Ethernet IP
Address
Modbus
Address
Configuration
(Other)
Data Type
Value
Mode Lower
Range
Higher
Range
N67:6
40616 Process Con-
trol Type
ENUM
0 = Temperature
Read
NA
NA
1 = Pressure
N67:7
40617
Discharge
Pressure Con-
trol Available
INT
0 = No, 1 = Yes
Read
NA
NA
N67:8
40618
Discharge
Pressure
Control # of
Setpoints
INT
0 = No, 1 = Yes
Read
NA
NA
N67:9
40619 Restart on
Power Fail
ENUM
(Currently Unused)
Read-
Write
NA
NA
N67:10
40620 Oil Monitor-
ing
ENUM
0 = No Oil Filter Monitoring
Read
NA
NA
1 = Only Oil Filter In
2 = Oil Filter In and Oil Filter Out
N67:11
40621 Oil Level Trip
Available
INT
0 = No, 1 = Yes
Read
NA
NA
N67:12
40622
Anti-Recycle
ENUM
0 = True Anti-Recycle
Read
NA
NA
1 = Accumulative Anti-Recycle
2 = Hot Starts
N67:13
40623 Compressor
Sequencing
INT
(Currently Unused)
Read
NA
NA
N67:14
40624 Idle Time Trip
INT
0 = No, 1 = Yes
Read
NA
NA
N67:15
40625 On Communi-
cation Failure
ENUM
0 = Revert to Local Control
Read
NA
NA
1 = Stop with Alarm
N67:16
40626 Panel ID
INT
Read
NA
NA