5 – 10
Section 5
•
Compressor Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Oil Control
This setpoint defines how the MicroVission will manage
the crankcase’s oil. When the compressor is used in cold
climatic conditions, it might be possible that compres-
sor does not start due to low crankcase oil temperature.
Oil Crankcase Heater Temperature
• When the oil temperature falls below this setpoint,
the oil heater (7th Digital Channel on Multi IO Board)
will turn ON. Note, there is a 2°F differential associ-
ated with this setpoint. For example, when set at
100 °F, the oil heater will turn ON at 98 °F and turn
OFF at 102 °F.
Figure 5-9. Compressor Control Screen - Oil Control
Содержание Vilter MicroVission
Страница 1: ...MicroVission Controller Operation and service manual Version 1 0 ...
Страница 2: ......
Страница 4: ......
Страница 115: ......