Appendix A
•
Unloaders
A – 4
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table A-9. Type 9 Unloader - Cylinders: 6 or 12
Unloading Percentage: 17%, 33%, 50%, 66%, 83%
Single cylinder on Unloader Output #1 *
% Load
Compressor Start Output Unloader Output
#1 (single cylinder)
Unloader Output #2
(double cylinder)
Unloader Output #3
(double cylinder)
% Unload
0 (OFF)
0
0
0
0
100
17
1
1
1
1
83
33
1
0
1
1
66
50
1
1
0
1
50
66
1
0
0
1
33
83
1
1
0
0
17
100
1
0
0
0
0
Table A-10. Type 10 Unloader - Cylinders: 7
Unloading Percentage: 29%, 57% *
% Load
Compressor Start Output Unloader Output #1 Unloader Output #2
% Unload
0 (OFF)
0
0
0
100
43
1
1
1
57
71
1
0
1
29
100
1
0
0
0
Table A-11. Type 11 - Compressor with no Unloading *
% Load
Compressor Start Output
0 (OFF)
0
100
1
Table A-12. Type 12 Unloader - Cylinders: 3
Unloading Percentage: 33% *
% Load
Compressor Start Output Unloader Output #1
(single cylinder)
% Unload
0 (OFF)
0
0
100
66
1
1
33
100
1
0
0
* 0 = output OFF
1 = output ON