B - 8
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-10. Commands Block
Ethernet IP
Address
Modbus
Address
Commands
Data Type
Value
Mode Lower
Range
Higher
Range
N56:0
40170 Alarm Reset
INT
1 = Perform Reset
Read-
Write
NA
NA
N56:1
40171
Active Remote Control
ENUM
0 = None (Local)
1 = Direct I/O
2 = Serial
3 = Ethernet
Read-
Write
NA
NA
N56:2
40172 Remote Control Select
ENUM
0 = Auto Control
1 = Step Load / Unload
Read-
Write
NA
NA
N56:3
40173 Auto Control Type
ENUM
0 = Suction Pressure
(if enabled)
1 = Process Control
(if enabled)
2 = Discharge Pressure
(if enabled)
Read-
Write
NA
NA
N56:4
40174 Remote Step Load
INT
1 - Load
Read-
Write
NA
NA
N56:5
40175 Remote Step Unload
INT
1 - Unload
Read-
Write
NA
NA
N56:6
40176 Step Hold %
INT
Currently Unused
Read-
Write
NA
NA
N56:7
40177
Active Setpoint
ENUM
1 = Setpoint 1
2 = Setpoint 2
(if enabled)
Read-
Write
NA
NA
N56:8
40178 Start Command
INT
1 = Remote Auto
Read-
Write
NA
NA
N56:9
40179 Stop Command
INT
1 = Stop
Read-
Write
NA
NA
N56:10
40180 Auto-Cycle Enable/ Disable
INT
0 = Disable
1 = Enable
Read-
Write
NA
NA
NOTE
Commands: Start Command – starts the compressor in the currently active control mode. If anti-recycle time exists,