B - 15
Appendix B
•
Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Table B-19. Timers Block (Page 2)
Ethernet IP
Address
Modbus
Address
Timers (Page 2)
Data Type
Value
Mode Lower
Range
Higher
Range
N65:0
40520
Communication Failure
Detect Timer (minutes)
INT
Read
NA
NA
N65:1
40521 Restart Power Failure
Timer (minutes)
INT
(Currently
Unused)
Read
NA
NA
N65:2
40522
True Anti-Recycle Timer
(minutes)
INT
Read-
Write
6
60
N65:3
40523
Accumulative Anti-Recycle
Timer (minutes)
INT
Read-
Write
6
60
N65:4
40524 Hot Starts per Hour
INT
Read-
Write
1
10
N65:5
40525 Oil Recovery Solenoid
Shutoff Delay (seconds)
INT
Read
NA
NA
N65:6
40526 Low Oil Level Alarm Delay
(seconds)
INT
Read
NA
NA
N65:7
40527 Low Oil Level Trip Delay
(seconds)
INT
Read
NA
NA
Table B-20. Configuration (Time) Block
Ethernet IP
Address
Modbus
Address
Configuration (Time)
Data Type Value
Mode
Lower
Range
Higher
Range
N66:0
40600
Time – Hours
INT
(HH)
Read-
Write
0
23
N66:1
40601
Time – Min
INT
(MM)
Read-
Write
0
59
N66:2
40602
Time – Secs
INT
(SS)
Read-
Write
0
59
N66:3
40603
Date – Year
INT
(YYYY)
Read-
Write
1970
2037
N66:4
40604
Date – Month
INT
(1-12)
Read-
Write
1
12
N66:5
40605
Date – Day
INT
(1-31)
Read-
Write
1
31