13 – 5
Section 13
•
Data Backup
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV
Restore Original Database to New SD card
Now that the new card is inserted, power up the
MicroVission panel. The MicroVission boots up in a min-
ute or so.
• Once the MicroVission is booted up, press on the
“User Access” button.
• Insert the thumb drive in to the USB port.
• Navigate to the Data Backup screen. You should
again see the USB thumb drive listed in the “Available
Devices” window.
• Select the Load function (above the “Available
Devices” field), and then highlight the device that is
listed in the “Available Devices” window.
• In the “Select Folder/File” window, find the backup
file for this compressor, and highlight it.
• Now press the “Load” button.
a) A pop-up window will appear with a message
Loading new databases will require a program
restart. Continue?”. Press “Yes”.
b) Another pop-up window might appear with
a message “One or more settings selected for
loading were missing from the archive. And it
will list what is missing. Continue loading any-
way?”. Press “Yes”.
c) Another pop-up box might appear with a
message asking if you want to use the IP address
it found. Press “OK”.
• A pop-up box appears with a message “Settings
were successfully loaded. Program will restart”.
Press “OK“.
When the OK button is pressed, the panel will reboot.
Now using the “hand documented” settings that you re-
corded, compare the setpoints on that list against those
in the MicroVission. They should all be OK. Here are the
KNOWN issues that we have found with this procedure.
• If you have communication connection issues after
restoring the database, you may have to “re-enter”
the IP address that is shown on page 3 of the con-
figuration screen. If you experience problems after
the “Restore” function – then re-enter your commu-
nication settings.
Record Operating Setpoints And Configuration
Information
Before powering down the MicroVission to replace the
SD card, copy the following operating setpoints and
configuration information.
1. Configuration Screen - Page 1
a. No. of Cylinders and No. of Unloaders
b. Compressor Control Type & Number of
Controllers
c. Oil Monitoring Settings
d. Anti-Recycle Settings
2. Configuration Screen - Page 2
a. Order Number
3. Configuration Screen - Page 3
a. Active Remote Control Setting
b. If Active Remote Control = Direct I/O, docu-
ment “type” of Direct I/O selection.
c. Ethernet Settings
4. Configuration Screen, Page 5
a. Optional I/O boards
5. Compressor Control Setpoints – all
6. Alarms and Trips Setpoints – all
7. Timer Setpoints – all
8. Instrument Calibration, Pressure page
a. Record Transducer Range selection for Suction
Pressure, Discharge Pressure, Oil Pressure, Filter
Inlet Pressure & Filter Outlet Pressure.
b.Record ‘Total Offset” value for Suction
Pressure, Discharge Pressure, Oil Pressure, Filter
Inlet Pressure & Filter Outlet Pressure.
9. Instrument Calibration - Temperature page
a. Record Transducer Range selection for
Suction Temperature, Discharge Temperature,
Oil Temperature & Process Temperature
b. Record “Total Offset” value for Suction
Temperature, Discharge Temperature, Oil
Temperature & Process Temperature
10. Instrument Calibration – Motor Current Settings
11. Compressor Runtime.