Section 6 • Alarms and Trips
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.0
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
High Discharge #2 Temperature:
Below Messages will be displayed on Main Screen when Discharge #2 Temperature value rises above configured
setpoints. Refer Figure 6- 2 for Alarm & Trip setpoints.
These safeties will be only active if below two conditions are met:
1)
When No. of Cylinders set in Configuration screen is “12 cyl” or “16 cyl”.
2)
High Discharge Temp Bypass Timer is lapsed.
High Discharge 2
Temperature Warning
High Discharge 2
Temperature Inhibit
High Discharge 2
Temperature Alarm
High Discharge 2
Temperature Trip
Discharge #2 Temperature
>= High Discharge Tem
-
perature Alarm Setpoint
Discharge #2 Temperature >= High
Discharge Temperature Alarm
Setpoint
Discharge #2 Tempera-
ture >= High Discharge
Temperature Alarm
Setpoint
Discharge #2 Tempera-
ture >= High Discharge
Temperature Trip Set-
point
Remote Comm. Time-out:
Below Messages will be displayed on Main Screen when there is no remote communication to the MicroVission
for time as set in Compressor Failure Detect Timer. Refer Timers screen for setpoint.
Remote Comm. Time-out Alarm will be only monitored if “Revert to Local Control” option is set for On Commu
-
nication Failure setting in Configuration screen.
Remote Comm. Time-out Trip will be only monitored if “Stop Compressor with Trip” option is set for On Com
-
munication Failure setting in Configuration screen.
Remote Comm Time
out Alarm
Remote Comm Time out
Trip
Remote Comm. Inac-
tive Time >= Compres
-
sor Failure Detect
Timer
Remote Comm. Inactive
Time >= Compressor Fail
-
ure Detect Timer
Compressor Interlock:
Below message will be displayed on Main Screen in following cases:
1)
When Motor Auxiliary Contact Fails to Close during Compressor Start.
2)
When Motor Auxiliary Contact Opens when Compressor is Running.
Compressor Interlock Inhibit
Compressor Interlock Trip
Motor Auxiliary Contact Fails to
Close when Compressor is Starting
Motor Auxiliary Contact
Opens when Compressor
is Running