Options
Liebert
®
NXL
™
60
3.4.2 LBS Configurations
• Load Bus Sync – Enable or Disabled (default: Disable)
• LBS Master Select - Master or Slave (default: Slave)
• LBS Slave Priority – 0 to 7 (default: 0)
3.4.3 Normal Operations
The LBS will synchronize the Designated Slave Systems (DSS) to the Designated Master System
(DMS). The DSS will synchronize to the DMS output if the DMS is in Normal, Battery, Bypass or
Maintenance Bypass Mode
If the DSS transfers to Bypass Mode or Maintenance Bypass mode, the DMS will then synchronize to
the output bus of the DSS. This re-selection of master will be accomplished automatically.
3.4.4 Slave Priority
When Slave Priority is enabled, the LBS system will work the same as Normal operations (See
except when the DMS disqualifies it bypass source. If the DMS’s bypass is
disqualified, the LBS system will synchronize to the output of the DSS with the lowest Slave Priority
number that has a qualified bypass. The LBS system will synchronize back to the DMS when the
DMS’s bypass is qualified or all DSS’s bypass are disqualified.
If a DSS LBS Slave Priority is set to “0”, it will not assume the synchronization of the system if the
DMS disqualifies its bypass.
Figure 52 LBS configuration
3.4.5 Master System
The unit designated at power-up/reset to be the Master will monitor the LBS Sync Pulse line.
If two units are designated as Master, the second designated Master Unit to come on-line will inhibit
the LBS and synch to its own bypass.
The LBS Master will monitor the LBS Sync Pulse continuously; if the LBS Master detects that
another unit has transferred to bypass, the LBS Master will follow the unit on bypass.
• Slave can no longer follow the Master; the Master must follow the Slave.
When the Master unit is following a Slave LBS Sync Signal, it will generate the LBS Active event.
If the Slave LBS Sync Pulse stops, the Master will resume generating the LBS Sync Pulse.
NOTE
The LBS settings permit proper operation with only one UPS set as the Master unit.
NOTE
Setting of ‘0’ will disable LBS Slave Priority
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......