Operation
Liebert
®
NXL
™
32
2.15.2 Startup—N+1 System
The following instructions will start an individual UPS module. Repeat these steps for all the UPS
units in the system that will be started.
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
NOTICE
Risk of improper startup. May cause equipment damage.
These steps should be performed after the SCC startup has been initialized.
NOTICE
Risk of equipment damage. If an abnormal situation occurs during this startup procedure, open
the input circuit breaker and investigate the problem. Call Liebert Services if help is needed.
1. Before applying power to the UPS modules, determine the position of the following circuit
breakers and switches:
•
Input Circuit Breaker (CB1)
—Verify that this breaker on the front of the UPS cabinet
(
) is in the open position.
•
Module Battery Disconnect (MBD)
—Verify that this external breaker is open or tripped. If
DC source cabinets are used, verify that breakers on all the cabinets are open.
•
Output Circuit Breaker (CB2)
—This motorized circuit breaker (
) should be open.
•
Module Output Breaker (MOB)
Optional—This circuit breaker should be open. This breaker is
external to UPS, possibly in the paralleling gear.
2. Close the Rectifier Feed Breaker (RFB). This breaker is external to UPS, possibly in the
paralleling gear. The display touchscreen should start.
3. Close the MOB breaker, if present on the system.
4. Press the “Start-Up,” then the “Manual Start” menu button (see
). The “Close CB1”
message will appear.
5. Close CB1 (see
). The “Press OK to Issue Rectifier On Command” message will appear.
6. Press “OK.” This will start the UPS’ rectifier. The message “Press OK to Issue Inverter On
Command” will appear.
7. Press “OK.” The rectifier will be On and the Inverter will be on standby. The message “Press OK
to Issue MBD Enable Command” will appear.
8. Press “OK.”
!
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
If the UPS has been shut down for maintenance, verify that all of the UPS system doors are
closed and latched. All test equipment must be removed from the system. All electrical
connections must be secure
!
WARNING
Risk of electrical shock. Can cause equipment damage, personal injury and death.
The following procedure may provide power (with DC source available) to the critical load
distribution system. Verify that the critical load distribution is ready to accept power. Ensure
that personnel and equipment are ready for the critical load distribution system to be energized.
NOTE
If the system was shut down in response to an “Emergency Off,” there may be alarm messages
on the touchscreen that describe system conditions before or at the time of the shutdown. Some
or all of the alarm conditions may have been resolved.
To clear these alarm messages, turn Off control power (see
). Wait at least 10 minutes
for the control power circuitry to completely de-energize. After 10 minutes, turn control power
back On.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......