Introduction
Liebert
®
NXL
™
4
1.3
Options
A number of options are available from Liebert for your UPS system. (Some options are not available
for all ratings.) Described below are the most frequently provided options. Other options are
available. Contact your Liebert sales representative for more information.
•
Battery and Racks
—The batteries provide power in the event of a power outage. The Liebert
NXL UPS can use a variety of battery types, provided the battery plant is designed for the
UPS DC voltage range and the load requirements of your application.
•
Battery Cabinets
—Valve-regulated, lead-acid (VRLA) sealed batteries are available in
matching cabinets for convenient installation and maintenance in otherwise unprotected space.
Depending on the UPS module rating, two or more cabinets may be connected in parallel to
provide the additional run time. This option is required to complete the UPS system.
•
Module Battery Disconnect
—The UPS system utilizes a separate Module Battery Disconnect
for remotely located batteries. A sensing circuit in the UPS module, set at the battery low voltage
limit, trips the Module Battery Disconnect to safeguard the battery from excessive discharge. The
Module Battery Disconnect has an undervoltage release mechanism designed to ensure that
during any shutdown or failure mode all battery potential is removed from the UPS system.
•
Two Breaker Maintenance Bypass
—This switchboard provides make-before-break
maintenance bypass. It includes: Maintenance Bypass Breaker (MBB) and Maintenance Isolation
Breaker (MIB).
•
Load Bus Synchronization
—The Load Bus Sync (LBS) option keeps two or more independent
UPS systems (and therefore their critical load buses) in sync, even when the modules are
operating on DC source or asynchronous AC sources. This means that critical loads connected to
both load buses can switch seamlessly between the two.
•
Customer Alarm Interface
—This optional interface board allows the input and display of eight
alarms from customer-supplied contacts, each with a customer-selected name.
•
Temperature-Compensated Charging
—When the battery temperature exceeds a preset limit
(typically 77°F [25°C]), this optional circuit proportionally reduces float charging voltage to
prevent overcharging the battery.
•
Battery Load Testing
—When activated, this option forces the battery string to assume the load
for a short period of time.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......