Introduction
3
Liebert
®
NXL
™
1.2
Modes of Operation
1.2.1 Normal Mode
Operating in normal mode, the Liebert NXL’s rectifier derives power from a utility AC source and
supplies regulated DC power to the inverter, which regenerates precise AC power to supply the
connected equipment. The rectifier also uses the utility source power to charge the DC sources.
1.2.2 Bypass Mode
When the Liebert NXL is in bypass mode, the load is directly supported by utility power and is
without DC source backup protection.
The Liebert NXL’s inverter and bypass static switch will shift the load from the inverter to bypass
mode without an interruption in AC power if the inverter is synchronous with the bypass and any of
the following occurs:
• Inverter fails
• Inverter overload capacity is exceeded
• Inverter is manually turned off by the user
1.2.3 Battery Mode
When utility AC power fails, the Liebert NXL protects the critical load by instantaneously channeling
DC source power to the inverter, which continues supporting the critical load without interruption.
When utility power returns and is within acceptable limits, the Liebert NXL automatically shifts back
to Normal mode, with the rectifier powering the critical load.
1.2.4 Maintenance Bypass
The installation of a Maintenance Bypass Cabinet or Assembly is recommended to allow you to totally
isolate the UPS from all power sources. Use of the Maintenance Bypass is described in
.
1.2.5 ECO Mode
The ECO Mode feature improves the overall efficiency by powering the critical bus from the bypass
static switch instead of the inverter.
The user has the ability to start/stop ECO Mode manually via HMI or automatically based on time
and day of week schedule entries.
When the critical bus goes out of tolerance (voltage, frequency or slew rate), the BPSS is turned off
and the inverter powers the critical bus.
The inverter is always ready to take the load in the event that the bypass source fails.
1.2.6 Intelligent Paralleling
Intelligent Paralleling is intended to increase system efficiency and to reduce the operating hours on
the modules. Intelligent Paralleling will put one or more paralleled modules into standby operation
when the number of redundant modules is above the user-specified threshold, plus some hysteresis.
NOTE
If the inverter is asynchronous with the bypass, the static switch will transfer the load from the
inverter to the bypass WITH interruption in AC power to the critical load. This interruption
will be less than 10ms. This interruption time may be altered by modifying the Output transfer
interrupt time setting.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......