UPS Alarm and Status Messages
Liebert
®
NXL
™
94
Manual
Xfer
Inhibit
This summary event means the conditions
required to perform a manual transfer to bypass
are not met (Inverter must be in sync with
bypass).
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
The condition clears from the Active Event Window
when manual transfers are enabled.
A possible reason for this condition is an unstable
generator. If the generator frequency is not stable,
or not at 60 Hz, the Inverter may have difficulty
maintaining synchronization with the bypass
source.
To check the synchronization of the Inverter to
bypass, click “Transfer” and observe the
synchroscope. A non-sync condition is indicated by
a varying phase angle error, rather than a stable
“0” degree indication.
If the unit is not on generator, and the bypass
voltage otherwise appears normal, contact your
factory-authorized service provider.
Parametric Data (Note 1)
Bit
Reason
0x0001
Bypass not Qualified
0x0002
Bypass to Output Phase Error
0x0004
Phase Error Exceeds Manual Transfer
Limit Setting
0x0008
Voltage Exceeds Manual Transfer Limit
Setting
0x0010
BFB is Open
0x0020
BPSS Board has Failed
0x0040
Bypass Sync Error
0x0080
Loss of Sync Pulse
0x0100
BPSS not Enabled
0x0200
Removing Module will cause Overload or
Drop the Load
0x0400
CB2 Open
0x0800
MOB Open
0x1000
Bypass Source Fault Detected
0x2000
Continuous Tie Active
Max Load
Alarm
Ph A
The user adjustable maximum load alarm
threshold was exceeded. This is a “notification
only” type alarm, meaning the UPS takes no
action other than sounding an audible alarm
based on this setpoint. The setting allows the
user to monitor the load status of the UPS.
For example, if the current load on Phase A is
50%, the user can set this setpoint to 80% and
an alarm is received if the added load exceeds
80%.
The alarm may also be configured with a delay,
to prevent nuisance alarms due to cycling loads.
The alarm is self-clearing. Once the load level
decreases to less than 95% of the level setting,
the alarm clears.
Press “SILENCE” to silence the audible alarm.
Check the kW load % displayed for A phase.
To check the setpoint for the alarm, press “Config,”
“User Settings,” “Adjustable Setpoints,” “Max Load
Alarm.”
Compare the setpoint to the displayed load
percentage. If the load percentage displayed is
correct and the value exceeds the setpoint, raise
the setpoint to clear the alarm, or reduce the load
below the setpoint.
Contact your factory-authorized service provider.
Table 10
Liebert NXL alarm and status messages
(continued)
Event Message
Event Definition
Recommended Action
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......