Operation
Liebert
®
NXL
™
20
2.5
Startup Menu
This menu is used to start the UPS and individual devices.
Manual
—This will begin the UPS startup. See
2.15 - Manual Operations—All Systems
for
details.
Devices
• Close Trap—This will start the Input filter, if installed
• Close MBD/BCB—If the MBD is motor-operated, the Close command will enable and energize the
motor to close. If the MBD is not motorized, the Close command will enable the breaker UVR. The
MBD/BCB must be closed manually. If no MBD is selected, this setting is not displayed.
2.6
Shutdown Menu
This menu permits shutting down the UPS and individual devices. See
for details.
Open Trap
—Open the input trap filter
Open MBD/BCB
—Opens the associated MBD or BCB breaker
UPS
—Turns off inverter, rectifier and trips all DC source breakers. Transfers to bypass, if available.
Figure 22 UPS shutdown popup
System
—Turns off inverter, rectifier and trips all DC source breakers. Will shut down UPS
completely.
NOTICE
Risk of equipment damage. This command will result in the load being shut down.
The following popup window is displayed when the UPS is about to be shut down. To shut down the
UPS, an operator must press OK.
Figure 23 System shutdown popup
2.7
Transfer Menu
This menu permits switching between UPS and Bypass mode. A graph in the multipurpose window
shows if the UPS is in synch with the bypass. If the UPS and bypass are in synch, pressing
Bypass
will switch the UPS to Bypass mode. Pressing
UPS
will switch back to Normal (Inverter) Mode (see
2.15 - Manual Operations—All Systems
for details.
NOTE
The following popup window is displayed when the UPS is about to be shut down. To shut
down the UPS, an operator must press OK.
NOTE
If the bypass and UPS are out of synch range, the transfer buttons will be disabled.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......