Operation
Liebert
®
NXL
™
28
2.14.5 Emergency Module Off (Optional)
The Emergency Module Off (EMO) mode will transfer the critical load to the bypass line and remove
power from all UPS module components except the controls, bypass circuit breaker and the static
switch.
If installed, the Emergency Module Off control is a guarded pad next to the display touchscreen
(
and
Lift the cover and press the pad. The load will be transferred to bypass, and the DC source (MBD),
input and output circuit breakers will be opened (tripped). Refer to
Figure 34 Emergency modules off
2.14.6 Remote Emergency Power Off
The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS
system. It usually is installed in the same room as the critical load equipment. This mode can also be
initiated by an automatic contact closure in the same external circuit as the manually operated
switch.
When the Remote Emergency Power Off switch is operated, all UPS circuit breakers are opened,
including the bypass circuit breaker. All power through the UPS is removed from the load. Typically,
the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS
controls. Refer to
2.15.13 - Shutdown—Single Module UPS System
Figure 35 Remote emergency power off
Bypass
DC Source
DC Bus
Module
Output
BFB
CB2
CB1
MBD
Input
Bypass
DC Source
DC Bus
Module
Output
BFB
CB2
CB1
MBD
Input
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......