Options
Liebert
®
NXL
™
66
3.6.6 Module Standby Rotation
Module Standby Rotation will limit the time a module is in standby operation when the Number of
Redundant Modules doesn't change for a long period.
• The module selected as the next to terminate Intelligent Paralleling per Module Selection -
Termination, (see
Intelligent Paralleling Module Termination on page 65
), will not be in
standby operation for longer than Maximum Time Module In Standby (see
).
• When this time expires, the module will terminate Intelligent Paralleling and come back online.
• The next module selected to activate Intelligent Paralleling will be put into standby operation.
NOTE
When Maximum Time Module In Standby setting is 0, Module Standby Rotation is disabled.