UPS Alarm and Status Messages
95
Liebert
®
NXL
™
Max Load
Alarm Ph B
The user adjustable maximum load alarm
threshold was exceeded. This is a “notification
only” type alarm, meaning the UPS takes no
action other than sounding an audible alarm
based on this setpoint. The setting allows the
user to monitor the load status of the UPS.
For example, if the current load on Phase B is
50%, the user can set this setpoint to 80% and
an alarm is received if the added load exceeds
80%.
The alarm may also be configured with a delay,
to prevent nuisance alarms due to cycling loads.
The alarm is self-clearing. Once the load level
decreases to less than 95% of the level setting,
the alarm clears.
Press “SILENCE” to silence the audible alarm.
Check the kW load % displayed for B phase.
To check the setpoint for the alarm, press “Config,”
“User Settings,” “Adjustable Setpoints,” “Max Load
Alarm.”
Compare the setpoint to the displayed load
percentage. If the load percentage displayed is
correct and the value exceeds the setpoint, raise
the setpoint to clear the alarm, or reduce the load
below the setpoint.
Contact your factory-authorized service provider.
Max Load
Alarm Ph C
The user adjustable maximum load alarm
threshold was exceeded. This is a “notification
only” type alarm, meaning the UPS takes no
action other than sounding an audible alarm
based on this setpoint. The setting allows the
user to monitor the load status of the UPS.
For example, if the current load on Phase C is
50%, the user can set this setpoint to 80% and
an alarm is received if the added load exceeds
80%.
The alarm may also be configured with a delay,
to prevent nuisance alarms due to cycling loads.
The alarm is self-clearing. Once the load level
decreases to less than 95% of the level setting,
the alarm clears.
Press “SILENCE” to silence the audible alarm.
Check the kW load % displayed for C phase.
To check the setpoint for the alarm, press “Config,”
“User Settings,” “Adjustable Setpoints,” “Max Load
Alarm.”
Compare the setpoint to the displayed load
percentage. If the load percentage displayed is
correct and the value exceeds the setpoint, raise
the setpoint to clear the alarm, or reduce the load
below the setpoint.
Contact your factory-authorized service provider.
MBD
Open
The Module Battery Disconnect is open.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the status of Module Battery Disconnect
(MBD). If it is open, the alarm is normal.
If the Module Battery Disconnect is closed, contact
your factory-authorized service provider.
MMS
Pwr Share
Warn
This event indicates that in a multi-module
system, a module determines that at least one
phase is not sharing the power within some
threshold as compared to the per phase average
power of all the other modules.
This alarm is self clearing.
Press “SILENCE” to silence the audible alarm.
Wait 30 seconds and check to see if the alarm has
cleared.
If the alarm does not clear after 30 seconds, check
the Event Log by pressing “Status Reports,” “Event
Log” for additional information and contact your
factory-authorized service provider.
MMS
Rexfer
Inhibit
This summary event means the conditions
required to perform a transfer to inverter are not
met.
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
The condition clears from the Active Event Window
when manual retransfers are enabled.
Possible reasons for this condition are:
1.
With the
collective not on UPS inverters and Module Output
Breaker (MOB) open (if installed) active or Output
Isolator (QE) open (if installed) active or
2.
Manual
Retransfer Inhibit is active or
3.
Not enough
inverters are available to support the measured
load or
4.
Any module's inverter is connected to the
collective.
Table 10
Liebert NXL alarm and status messages
(continued)
Event Message
Event Definition
Recommended Action
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......