3.5.3 Bypass Qualification limits
All of the following conditions must be true to qualify ECO Mode operations based on the bypass
source:
• Bypass voltage is within Manual Transfer Bypass Voltage High Limit setting and Manual
Transfer Bypass Voltage Low Limit setting or Max Bypass range of ±10%
• Bypass Frequency is within the Bypass Tracking Window setting
• Bypass is within the slew limits per Bypass Tracking Slew Rate setting
• Bypass Sync Error event is not active
• Backfeed Breaker is closed
• Bypass Static Switch Unable event is not active
3.5.4 Conditions to Activate ECO Mode
All the following conditions must be satisfied to start ECO Mode
• ECO Mode Session is active
• Bypass Source Qualification is satisfied
• The Load On UPS event must be active for a short, specified amount of time
• Input Contact Interface 1 (Channel 8) event is not active
• Load is greater than 10%
3.5.5 Conditions to Suspend ECO Mode
The system will suspend ECO Mode when at least one of the following conditions is true:
1. Bypass Source Qualification is not satisfied.
2. Input Contact Interface 1 (Channel 8) event active.
3. On Generator Active event is active.
4. Load kW is less than 10%.
When any Conditions to Suspend have been satisfied, the inverter(s) will power the load and the
bypass will be turned off. When the Conditions to Activate ECO Mode (Section 3.5.4) have been met,
the system will automatically return to ECO Mode.
3.5.6 Conditions to Terminate ECO Mode
The system will terminate ECO Mode when at least one of the following conditions is true:
1. ECO Mode - Stop command is received.
2. Scheduling stop time is reached.
3. Excessive ECO Mode Suspension event is set.
4. ECO Mode Operation setting is disabled.
5. System transfers to bypass, either automatically or manually.
6. Backfeed Breaker Open event is active.
7. Bypass Static Switch Unable event is active (SCR Short, SCR Open).
8. Inverter Output Breaker (CB2/IOB) Open event is active.
9. Module Output Breaker (MOB) Open event is active.
10. Critical Bus Voltage Disqualification is satisfied.
11. Bypass Line Fault or Critical Bus Load Fault detected.
When any Conditions to Terminate have been satisfied, the inverter(s) will power the load and the
bypass will be turned off. ECO Mode will not turn on until the next Start command - either manually
or automatically if scheduled.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......