UPS Alarm and Status Messages
97
Liebert
®
NXL
™
Outlet
Ovtemp
Limit
The difference between the inlet air temperature
and the outlet air temperature is too great.
This alarm means excessive heat is being
generated internally resulting in a higher than
normal exhaust air temperature.
If the Bypass is within limits, the UPS reacts to
this alarm by transferring to Bypass and shutting
Off the Inverter.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the Inlet Air Temperature on the One-Line
Display and verify the reading is accurate, i.e. is
the room temperature warmer than normal?
If the room temperature is warmer than normal,
investigate and resolve the issue.
If the room temperature is normal, and the Inlet Air
Temp reading on the One-Line Display is higher
than normal, contact your factory-authorized
service provider.
Output
Fault
This summary event occurs when the detected
system output exceeds acceptable voltage limits.
If the UPS was on Inverter at the time of the
event, the UPS transfers to bypass provided the
bypass voltage is available.
If the UPS was on bypass at the time of the
event, the UPS shuts down rather than allowing
unacceptable voltage to reach the load.
Press “SILENCE” to silence the audible alarm.
Check the Active Event Window and investigate
other events to further analyze.
Press “RESET” to attempt to reset any latched
events.
Check the One-Line Display to determine the
system status (On UPS, Bypass, or Off).
Check the input and bypass (dual input only) and
observe the One-Line color. Green indicates good
power present, orange means power is present but
outside nominal range, and gray means power is
not present.
If the load is Off and the input voltage is ok,
attempt to restart the UPS by pressing “Startup,”
“Manual Start,” and follow the prompts.
If the Input Meter indicates input or bypass is not
available, investigate and resolve the power
problem.
If the load is on bypass and all alarms are reset,
press “Transfer,” “UPS,” to attempt to transfer back
to Inverter.
If the issue cannot be resolved, contact your
factory-authorized service provider.
Output
Over/Under
Frequency
The output frequency has exceeded the output
frequency limit of +/- 0.25 Hz within the bypass
frequency.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the frequency on the Output Meter. If the
frequency is outside the synchronization range,
investigate and resolve the issue.
This alarm is commonly the result of an inverter not
synchronized to the bypass frequency.
If output frequency error persists, contact your
factory-authorized service provider.
Parallel
Comm
Warn
The control has detected a communication
failure on one of the redundant communication
busses. One of the paralleling control
communication busses is no longer
communicating within the system.
Press “SILENCE” to silence the audible alarm.
Power
Supply
Fail
The controls have detected a problem with a
power supply. This is a summary event. There
are several power supplies, most of them
redundant. In most cases, the UPS can operate
normally even with a failed supply.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to clear the alarm.
Check the Active Event Window to check for other
events that might explain the Power Supply Fail
alarm. For example, if the bypass is not available,
a Power Supply Fail alarm is normal, because the
Bypass Power Supply has no input power.
Contact your factory-authorized service provider.
Table 10
Liebert NXL alarm and status messages
(continued)
Event Message
Event Definition
Recommended Action
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......