Operation
31
Liebert
®
NXL
™
c. Press OK to continue. This will energize the load on the UPS internal bypass. The message
“Close CB1” will appear.
and
). The “Press OK to Issue Rectifier On Command” message
will appear.
e. Press “OK.” This will start the UPS’s rectifier. Load is still on internal bypass. The message
“Press OK to Issue Inverter On Command” will appear.
f. Press “OK.” The rectifier will be On and the Inverter will be on standby. Load is still on
internal bypass. The message “Press OK to Issue MBD Enable Command” will appear.
g. Press “OK.”
h. Close all battery/DC breakers. The UPS will stay in this mode until all breakers are closed.
If the DC sources are not ready to be started up, skip this command. The DC breakers can be
closed individually from the startup command at a later time (see
The message “Press OK to Issue Transfer Command” will appear.
i.
Press “OK.” The load is now energized from the UPS inverter.
NOTICE
Risk of equipment damage. If an abnormal situation occurs during this startup procedure, open
the input circuit breaker and investigate the problem. Call Liebert Services if help is required.
Figure 37 Startup commands
NOTE
The DC source charge current may increase quickly, but should slowly decrease. If the system
is recovering from a DC source shutdown or an input power failure, the UPS rectifier will be
recharging the DC source. Recharge current can be more than 100A. The maximum allowable
recharge current for any unit depends on the kVA rating and the DC source recharge current
limit.
!
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries. Refer to the battery
manufacturer’s manual, available on the manufacturer’s Web site, for specific information
about equalize charging.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......