44 Chapter 7 Application Guidance
EV3200 Door Control Inverter User Manual
7. Switch on the inverter again, in first time operation (OD or CD), the inverter will operate at the speed set by F3.00. When
the door is opened or closed completely, the inverter will switch to OD (or CD) completion torque maintaining status.
8. Set relevant parameters according to Table 7-4. The CD and OD parameters can be adjusted according to Figure 6-8 and
Figure 6-9.
9. Set F0.02 to 2 (terminal control mode), and the inverter can work normally.
7.5.3 Parameter Settings
Figure 7-4 provides the parameter settings.
Table 7-4 Parameter settings for distance control 3
Function code
Name
Setting
Remark
F0.01
Control mode
1
Distance control 1
F5.00
Function selection for control terminal X1
2
Normally open input contacts for light curtain signal
F5.01
Function selection for control terminal X2
4
Normally open input contacts for safety edge
F5.02
Function selection for control terminal X3
6
Normally open input for OD position limiting
F5.03
Function selection for control terminal X4
8
Normally open input for CD position limiting
F5.05
Function of programmable relay output PA1/PC1
2
Output signal 1 for complete OD
F5.06
Function of programmable relay output PA2/PC2
3
Output signal 1 for complete CD
F1.01
OD start creep distance for distance control
15%
F1.02
OD start creep speed
7Hz
F1.03
OD Acc time
0.5s
F1.04
OD reference frequency
20Hz
F1.05
Rush hour operation OD speed
25Hz
F1.06
OD speed decrease point in distance control
70.0%
F1.07
OD Dec time
0.5s
F1.08
OD ending creep speed
3Hz
F1.09
OD position limit in distance control
95.0%
F1.10
Threshold for OD torque changing
50.0%
F1.11
Maintaining torque at OD completion
50.0%
F1.12
OD operation curve selection in distance control
0
Parameters in this table are factory settings, adjust the
OD parameters according to the actual OD operating
conditions
F2.01
CD start creep distance
15%
F2.02
CD start creep speed
6Hz
F2.03
CD Acc time
0.5s
F2.04
CD reference frequency
15Hz
F2.05
Rush hour operation CD speed
20Hz
F2.06
CD speed decrease point in distance control
70.0%
F2.07
CD Dec time
2.0s
F2.08
CD ending creep speed
2Hz
F2.09
CD position limit in distance control
95.0%
F2.10
Threshold for CD torque changing
50.0%
F2.11
Maintaining torque at CD completion
50.0%
F2.12
CD high speed for EFS
10Hz
F2.13
CD operation curve selection in distance control
0
Parameters in this table are factory settings, adjust the
CD parameters according to the actual CD operating
conditions
F3.00
INI operation speed
5Hz
F3.08
CD obstruction sensitivity
100%
F3.09
Dec time upon abnormality
300ms
F3.10
OD obstruction sensitivity
100%
Parameters in this table are factory settings, adjust the
parameters according to the actual conditions