28 Chapter 6 Parameter Description
EV3200 Door Control Inverter User Manual
be completed, the operation time may exceed F3.01, and
OD error (E030) will be activated. E029 will be activated if
OD overtime occurred during the door width auto-learning.
When you set F3.01 to 0 or 3600, that is, set the OD time
limit to infinity, F3.01 is invalid.
F3.02 CD time limit
Setting range: 0 ~ 3600s
【
300s
】
Defines the maximum time of CD operation. You should set
it properly according to the actual conditions. The setting
must be bigger or equal to the sum of all the settings of CD
(parameter group of CD curve), otherwise error may occur
(E028). Setting F3.02 correctly can protect the system
against abnormal operation of elevator door. Normal
operation time will not exceed F3.02, but when the CD
position limit is invalid and causes the CD process unable to
be completed, the operation time may exceed F3.02, and
CD error (E031) will be activated. E029 will be activated if
OD overtime occurred during the door width auto-learning.
When you set F3.02 to 0 or 3600, that is, set the CD time
limit to infinity, F3.02 is invalid.
F3.03 Slow speed
operation time limit
Setting range: 0 ~ 3600s
【
400s
】
Defines the maximum time of slow OD and CD operation
when slow operation enable signal is active. You should set
it properly according to the actual conditions. The setting
must be bigger or equal to the sum of all the settings of OD
or CD (parameter group of OD curve and CD curve),
otherwise error may occur (E028). Setting F3.03 correctly
can protect the system against abnormal slow operation of
elevator door. Normal operation time will not exceed F3.03,
but when the OD or CD position limit is invalid and causes
the OD or CD process unable to be completed, the
operation time may exceed F3.03, and OD or CD error
(E030, E031) will be activated. When you set F3.03 to 0 or
3600, that is, set the OD or CD time limit to infinity, F3.03 is
invalid.
F3.04 Delay time for external OD
command
Setting range: 0 ~ 9999s
【
0s
】
Defines the time interval from the OD command becoming
invalid to the end of maintaining time of complete OD state.
If the maintaining time is equal to or greater than F3.04, the
inverter will stop. If the door is not opened to the position
completely and OD command is cancelled at that time, the
inverter will stop immediately and the delay function is
invalid. If F3.04 is set to 9999, the OD delay, once triggered,
will be maintained endlessly.
F3.05 Delay time for external CD
command
Setting range: 0 ~ 9999s
【
0s
】
Defines the time interval from the CD command becoming
invalid to the end of maintaining time of complete CD state.
If the maintaining time is equal to or greater than F3.05, the
inverter will stop. If the door is not closed to the position
completely and CD command is cancelled at that time, the
inverter will stop immediately and the delay function is
invalid. If F3.05 is set to 9999, the CD delay, once triggered,
will be maintained endlessly.
F3.06 Position of safety edge lift
signal output
Setting range: 0% ~
40.0%(door width)
【
10%
】
When the door position
≤
F3.06 × door width, safety edge lift
is needed. In this case, if safety edge lift signal output
function is configured, safety edge lift signal will be activated.
when the door position
≥
F3.07 × door width, safety edge lift
signal will not be activated.
CD
OD
Door width
F3.06
×
door width
Safety edge
lift signal output
Figure 6-11 Safety edge lift signal output position
F3.07 Function selection of OD
upon CD obstruction
Setting range: 0 ~ 1
【
1
】
Defines the handling method in the case CD process is
obstructed.
0: stop. The CD process can continue only after 10s, unless
OD operation is conducted within 10s.
1: re-open the elevator door
F3.08 CD obstruction
sensitivity
Setting range: 0 ~ 150%
【
100%
】
During CD process, the motor's output torque is detected in
real time. When the output torque is bigger than or equal to
the product of F3.08 and motor rated torque, it is regarded
that the CD process is obstructed, and the situation will be
addressed according to the setting of F3.07
When set to 0, CD obstruction sensing is disabled.
F3.09 Dec time upon
abnormality
Setting range: 10 ~ 2500ms
【
300ms
】
Defines the time taken for the inverter to decelerate from
current CD speed to zero in the case CD process is
obstructed.
Under the precondition of no over-current in Dec process,
F3.09 should be set as small as possible.
F3.10 OD obstruction
sensitivity
Setting range: 0 ~ 150%
【
0%
】
During CD process, the motor's output torque is detected in
real time. When the output torque is bigger than or equal to
the product of F3.10 and motor rated torque, it is regarded
that the OD process is obstructed, the inverter will stop
immediately. The door can be opened 10s later, or if CD
operation is implemented within 10s.
When set to 0, OD obstruction sensing is disabled.