40
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
Unit object 66: g/m³
5.9.
Comfort field
The
Sensor KNX AQS/TH-B-UP
can send a message to the bus if the limits of the
comfort field are exceeded. In this way, it is for example possible to monitor compli-
ance with DIN 1946 (standard values) or even to define your own comfort field.
Temperature hysteresis: 1°C
Relative humidity hysteresis: 2% rH
Absolute humidity hysteresis: 2 g/kg
5.10. CO2 PI control
If you activate air quality control, you can use the following settings to define control
type, target values, and ventilation.
Send behaviour
• never
• periodically
• on change
• on change and periodically
From change of
(is only sent if "on change" is selected)
0.1 g • 0.2 g • 0.5 g • 1.0 g • 2.0 g • 5.0 g
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h
Use comfort field
No • Yes
Send behaviour
• never
• periodically
• on change
• on change and periodically
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40; 26
Minimum temperature in °C
(Standard 20°C)
10 ... 21; 20
Maximum relative humidity in %
(
Standard 65%)
52 ... 90; 65
Minimum relative humidity in %
(Standard 30%)
10 ... 43; 30
Maximum absolute humidity in 0.1 g/kg
(Standard 115 g/kg)
50 ... 200; 115
Use control
Yes
• No