29
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
If the comfort set point is used as the basis, a dead zone is determined for the control
mode "heating
and
cooling" to avoid direct switching from heating to cooling.
Set point for standby
Standby mode is usually used for daytime mode when people are absent.
If set point values are entered separately:
A starting set point value is defined as well as a temperature range in which the nom-
inal value may be modified.
If the comfort set point value is used as a basis:
If the comfort set point value is used as a basis, the deviation from this value is set.
Eco set point
Eco mode is usually used for night mode.
If set point values are entered separately:
A starting set point value is defined as well as a temperature range in which the nom-
inal value may be modified.
Min. object value heating/cooling (in 0.1
°C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Dead zone between heating and cooling
only if both heating AND cooling are used.
1…100; 50
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
-300…800; 210
Min. object value heating/cooling (in 0.1
°C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Reduce nominal heating value (in 0.1°C)
for heating
0…200; 30
Increase nominal cooling value\r\n (in
0.1°C)
for cooling
0…200; 30
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
-300…800; 210
Min. object value heating/cooling (in 0.1
°C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280