13
Transfer protocol
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
4.
Transfer protocol
Units:
Temperatures in degrees Celsius
Air humidity in %
Absolute air humidity in g/kg and/or g/m
3
CO
2
content in ppm
Variables in %
4.1.
List of all communications objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transfer
U
Update
No.
Name
Function
DPT
Flags
0
Software version
readable
217,001
C R T
1
Temperature/humidity malfunction
sensor
Output
1,001
C R T
2
CO2 sensor malfunction
Output
1,001
C R T
3
Outside temperature reading
Input
9,001
C W
4
Inside temperature reading
Output
9,001
C R T
5
Overall temperature reading
Output
9,001
C R T
6
Min./max. temperature value request
Input
1,017
C W
7
Minimum temperature reading
Output
9,001
C R T
8
Maximum temperature reading
Output
9,001
C R T
9
Reset min./max. temperature value
Input
1,017
C W
10
Temp. threshold value 1: Absolute
value
Input/Output
9,001
C R W T
U
11
Temp. threshold value 1: (1:+ | 0:-)
Input
1,002
C W
12
Temp. threshold value 1:
Switching delay from 0 to 1
Input
7,005
C W
13
Temp. threshold value 1:
Switching delay from 1 to 0
Input
7,005
C W
14
Temp. threshold value 1: Switching
output
Output
1,001
C R T
15
Temp. threshold value 1:
Switching output block
Input
1,002
C W