16
Transfer protocol
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
70
Humidity threshold value 1: Switch-
ing output
Output
1,001
C R T
71
Humidity threshold value 1: Switch-
ing output block
Input
1,002
C W
72
Humidity threshold value 2: Absolute
value
Input/Output
9,007
C R W T
U
73
Humidity threshold value 2: (1:+ | 0:-)
Input
1,002
C W
74
Humidity threshold value 2: Switch-
ing delay from 0 to 1
Input
7,005
C W
75
Humidity threshold value 2: Switch-
ing delay from 1 to 0
Input
7,005
C W
76
Humidity threshold value 2: Switch-
ing output
Output
1,001
C R T
77
Humidity threshold value 2: Switch-
ing output block
Input
1,002
C W
78
Humidity controller: Blocking object
Input
1,002
C W
79
Humidity controller: Target value
Input/Output
9,007
C R W T
80
Humidity controller: Target value (1:+
| 0:-)
Input
1,002
C W
81
Humidity controller: Control variable
dehumidification (stage 1)
Output
5,001
C R T
82
Humidity controller: Control variable
dehumidification stage 2
Output
5,001
C R T
83
Humidity controller: Control variable
humidification
Output
5,001
C R T
84
Humidity controller: Dehumidification
1 status (1=ON | 0=OFF)
Output
1,001
C R T
85
Humidity controller: Dehumidification
2 status (1=ON | 0=OFF)
Output
1,001
C R T
86
Humidity controller: Humidification
status (1=ON | 0=OFF)
Output
1,001
C R T
87
Dewpoint temperature
Output
9,001
C R T
88
Coolant temp.: Threshold value
Output
9,001
C R T
89
Coolant temp.: Actual value
Input
9,001
C W
90
Coolant temp.: Offset change (1:+ | 0:-
)
Input
1,002
C W
91
Coolant temp.: Switching delay from
0 to 1
Input
7,005
C W
92
Coolant temp.: Switching delay from
1 to 0
Input
7,005
C W
93
Coolant temp.: Switching output
Output
1,001
C R T
No.
Name
Function
DPT
Flags