28
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
5.5.1. General set point values
You may enter separate set point values for each mode or use the comfort set point as
a basic value.
If you are using the controls for both heating
and
cooling, you may also select the set-
ting "separately with switching object". Systems used for cooling in the summer and
for heating in the winter can thus be switched from one to the other.
If you are using the basic value, only the deviation from the comfort set point value is
listed for the other modes (e. g., 2°C less for standby mode).
The grades for the set point changes is predefined. Modifications may only remain ac-
tive temporarily (do not save) or remain saved even after voltage recovery (and pro-
gramming). This also applies to a comfort extension.
The control may be manually reset to comfort mode from eco, or night mode. This al-
lows the user to maintain the daily nominal value for a longer time, e.g. when having
guests. The duration of this comfort extension period is set. After the comfort exten-
sion period is terminated, the system returns to eco mode.
Set point Comfort
Comfort mode is usually used for daytime mode when people are present. A starting
value is defined for the comfort set point as well as a temperature range in which the
nominal value may be modified.
Setting the nominal values
• separate with switching object
• separate without switching object
• with comfort set point as a basis
Behaviour of the switching object at value
only if switching object is used
• 0 = Heating | 1 = Cooling
• 1 = Heating | 0 = Cooling
Switching object value
before 1st communication
only if switching object is used
0 • 1
Grading for set point changes
(in 0.1 °C)
1… 50; 10
Saving set point value(s) and comfort
extension time
• not
• after voltage recovery
• after voltage recovery and
programming (do not use
for first start-up!)
Comfort extension time in seconds
(can only be activated from eco mode)
1…36000; 3600
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
not upon saving the set point value after
programming
-300…800; 210
Содержание KNX AQS TH-B-UP
Страница 5: ...4 Clarification of signs...