33
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
5.5.3. Cooling control level 1/2
If a cooling control mode is configured, one or two setting sections for the cooling lev-
els are displayed.
On the 1st level, cooling is controlled by a PI control which allows to either enter con-
trol parameters or select predetermined applications.
On the 2nd level (therefore only in case of a 2 level cooling), cooling is controlled via a
PI or a 2-point-control.
On level 2, the set point deviation between the two levels must furthermore be deter-
mined, i. e. the highest set point value from which the 2nd level is then added (when
values exceed this set point).
PI control with control parameters:
This setting allows individual input of the parameters for PI control.
Determine the deviation from the set point value which reaches maximum variable
value, i. e. the point at which maximum cooling power is activated.
The reset time shows how quickly the controls react to deviations from the set point
value. In case of a short reset time, the controls react with a fast increase of the varia-
ble. In case of a long reset time, the controls react somewhat more gently and needs
longer until the necessary variable for the set point deviation is reached.
You should set the time appropriate to the cooling system at this point (note manufac-
turer instructions).
Now determine what should be transmitted when the control is blocked.
Upon release, the control variable follows the rule again.
In case of a common variable for heating and cooling, 0 is always transmitted as a fixed
value.
Set point difference between levels 1 and 2
(in 0.1°C)
only for level 2
0…100; 40
Control type
only for level 2 and if no common variables
are used
• 2-point control
• PI control
Control type
•
PI control
Set control using
•
Controller parameter
• provided applications
Maximum control variable is reached
at set point/actual difference of (in °C)
0...5
Reset time (in min.)
1…255; 30
When blocked, the variable shall
• not be transmitted
• send a specific value
Value (in %)
only if a value is transmitted
0...100