39
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object. Define specifications here for the
behaviour of the output when blocked.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
5.8.
Absolute humidity
The absolute humidity value for the air is determined from the
KNX AQS/TH-B-UP
and can be output to the bus.
Unit object 65: g/kg
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before 1st communi-
cation
0 • 1
Behaviour of the switching output
With blocking
• Do not send message
• send 0
• send 1
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• If switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• If switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and
periodically
If switching output = 1
send 1
Switching output sends on change to 0 and
periodically
If switching output = 0
send 0
Use absolute humidity
No • Yes