Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
Threshold value setpoint using parameter:
Set the threshold values and hysteresis directly.
Threshold value setpoint using a communications object:
Beforehand, enter how the threshold value will be received from the bus. Basically, a
new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined which will be valid un-
til the 1st communication of a new threshold value. For units which have already been
taken into service, the last communicated threshold value can be used. Basically, a
temperature range is given in which the threshold value can be changed (object value
limit).
A set threshold value will be retained until a new value or a change is transferred. The
current value is saved in EEPROM, so that this is retained in the event of a power sup-
ply failure and will be available once the power supply is restored.
Threshold value setpoint using
Parameter
• Communications object
Temperature:
Threshold value in 0.1°C
Humidity:
Threshold value in % rH
CO2:
Threshold value in ppm
-300 … 800; 200
0...100; 70
0...5000; 1200
Hysteresis of the threshold value in %
0 … 50; 20
Threshold value setpoint using
Parameter •
Communications object
The last communicated value should be
retained
• never
• after restoration of power
• after restoration of power and
programming
Start threshold value
Temperature:
in 0.1°C
Humidity:
in % rH
CO2:
in ppm
valid till 1st communication
-300 … 800; 200
0...100; 70
0...5000; 1200
Object value limit (min)
Temperature:
in 0.1°C
Humidity:
in % rH
CO2:
in ppm
-300…800
0...100
0...5000
Object value limit (max)
Temperature:
in 0.1°C
Humidity:
in % rH
CO2:
in ppm
-300…800
0...100
0...5000
Type of threshold change
Absolute value • Increase/decrease
Step size
(upon increase/decrease change)
Temperature:
0.1°C • ... • 1°C • ... • 5°C
Humidity:
1.00% • 2.00% • 5.00% • 10.00%
CO2:
1 • 2 • 5 • 10 • 20 • 50 • 100 • 200
Hysteresis of the threshold value in %
0 … 50; 20