43
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
Now determine what should be sent when the control is blocked.
On release, the control variable follows the rule again.
5.11. Variable comparator
The two integrated control variable comparators can output maximum, minimum and
median values.
5.11.1. Control variable comparator 1/2
Determine what the control variable comparator should output, and activate the input
objects to be used. Send behaviour and blocks can also be set.
When blocked, the variable shall
• not be sent
• send a specific value
Value
(if a value is sent for one 1-bit object)
0 • 1
Value (in %)
(
(if a value is sent for an 8-bit object))
0...100
Use comparator 1/2
No • Yes
Output delivered
• Maximum value
• Minimum value
• Average value
Use input 1/2/3/4/5
No • Yes
Output sends
• on change of output
• on change of output and periodically
• when receiving an input object
• when receiving an input object and peri-
odically
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s • ... • 5 min • … • 2 h
From change of
(is only sent if "on change" is selected)
1% • 2% • 5% • 10% • 20% • 25%
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Blocking object value
before 1st communication
0 • 1
Behaviour of the switching output
With blocking
• do not send message
• Send value
Sent value in %
0 ... 100
on release, output is sent
(with 2 seconds release delay)
• the current value
• the current value after receipt of an object