8
Addressing of the device at the bus
Radio Actuator KNX RF S1R-B2 compact
• Version: 16.09.2020 • Technical changes and errors excepted.
Control of an external motor control unit with 24 V DC:
2.5. Instructions for assembly and operational
start-up.
Never expose actuators to water (e.g. rain) or dust. This can damage the electronics.
You must not exceed a relative air humidity of 80%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase last-
ing a few seconds. During this phase no information can be received or sent via the
bus.
For KNX devices with safety functions (e.g. wind or rain blocks), it is important to set
up periodical monitoring of the safety objects. The optimal ratio is 1:3 (example: if the
weather station sends a value every 5 minutes, the actuator must be configured for a
monitoring period of 15 minutes).
3.
Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another ad-
dress into the ETS by overwriting the 15.15.255 address or by teaching via the pro-
gramming button.
Direct current
(DC)
Motor control
unit
Manual switch input
Mains
(230 V AC)
Each terminal contact may
be loaded with a maximum
of 10 A.