32
Parameter setting
Radio Actuator KNX RF S1R-B2 compact
• Version: 16.09.2020 • from application 1.0 •
Technical changes and errors excepted.
Switch off delay
The switch off delay is set with a time basis and time factor (e.g. 1 min × 4 corresponds
to 4 minutes). Additionally it is specified if the time interval for a repeat receipt of a
switch-off telegram is extended ("can be triggered again", e.g. by pressing the button
again) and what happens when a switch off telegram arrives from the bus.
Staircase lighting timer
The staircase time switch sets with a time basis and time factor how long the light will
remain on (e.g. 1 s × 10 corresponds to 10 seconds). Additionally it is specified if the
time interval for a repeat receipt of a switch-on telegram is extended ("triggered again",
e.g. by pressing the button again) and what happens when a switch off telegram
arrives from the bus.
6.2.2.3.Blocking function (switch functions)
The menu item "blocking function" appears only for the settings for the switch function
channel if selected "Use blocking functions: Yes".
The output channel can be blocked by a block telegram. What happens during the
blocking, for bus voltage return and after the blocking is set here. The manual
operation is then not possible for an active block.
The function can be used for example for a light, which is turned on when pressing a
"panic button" (=trigger for blocking function) and cannot be turned off any longer.
Switch on delay cannot
be triggered again • can be triggered again
Off telegram during switch on-delay effects
nothing • direct turn off
Time basis
0.1 s • 1 s • 1 min • 1 h
Time factor
4...255; 10
Switch off delay cannot
be triggered again • can be triggered again
On telegram during switch off-delay effects
nothing • direct turn on
Time basis
0.1 s • 1 s • 1 min • 1 h
Time factor
4...255; 10
Staircase light time can
not be triggered again • can be triggered
again
Off telegram during staircase light period
affects
nothing • direct turn off
Blocking function blocks for
0 • 1
Value of the blocking object
after reset and ETS download
0 • 1
Response when blocking
no change • opened • closed
Response upon release
follows switch command • opened • closed