33
Parameter setting
Radio Actuator KNX RF S1R-B2 compact
• Version: 16.09.2020 • from application 1.0 •
Technical changes and errors excepted.
6.2.3. Button input (switch functions) - Input as bus button
Button inputs (drives) - Input as bus button
Correlation connection – time switch – block
Application 1: Staircase light at channel A1, that can only be switchable at twilight/
night (linking) and that is turned on during a fire alarm (blocking).
When switching via communication object "Channel A1 switch" (210), the light is
turned on or off normally. When switching via object "Channel A1 staircase light
function start" (215), the staircase light time function is activated. The time function has
priority, i.e. the status triggered by normal switching is overwritten.
210: Channel A1
Switching
with stair-
215: Channel A1
Switching
Input
Staircase light funct. Start
case light
217: Channel A1
Linking
Input
(from twilight sensor)
AND
Linking
213: Channel A1
Blocking object
input
(from smoke detector)
Block
211: Channel A1
Feedback
Output
Relay
function
function