10
Transfer protocol
Radio Actuator KNX RF S1R-B2 compact
• Version: 16.09.2020 • from application 1.0 •
Technical changes and errors excepted.
5.
Transfer protocol
5.1. List of all communication objects
Abbreviations:
R
Read
W Write
C
Communication
T
Transmit
DPT Data Point Type
No
Text
Function
Flags
DPT type
Size
1
Software version
readable
R-C-
[217.1]
DPT_Version
2 Bytes
100
Automatic or manual status
Output
R-CT
[1.1] DPT_Switch
1 Bit
101
Manual long-time
Input
RWC-
[1.8] DPT_UpDown
1 Bit
102
Manual short-time
Input
RWC-
[1.10] DPT_Start
1 Bit
103
Manual movement position
Input
RWC-
[5.1] DPT_Scaling
1 Byte
104
Manual blind position
Input
RWC-
[5.1] DPT_Scaling
1 Byte
105
Automatic long-time
Input
RWC-
[1.8] DPT_UpDown
1 Bit
106
Automatic short-time
Input
RWC-
[1.10] DPT_Start
1 Bit
107
Automatic movement
position
Input
RWC-
[5.1] DPT_Scaling
1 Byte
108
Automatic blind position
Input
RWC-
[5.1] DPT_Scaling
1 Byte
109
Change from manual to
automatic mode
Input
RWC-
[1.1] DPT_Switch
1 Bit
110
Automatic blocking object
Input
RWC-
[1.1] DPT_Switch
1 Bit
111
Current movement position
Output
R-CT
[5.1] DPT_Scaling
1 Byte
112
Current blind position
Output
R-CT
[5.1] DPT_Scaling
1 Byte
113
Object status
Output
R-CT
[1.1] DPT_Switch
1 Bit
114
Manually move to memory
position
Input
RWC-
[1.1] DPT_Switch
1 Bit
115
Learn object position
memory manually 0
Input
RWC-
[1.1] DPT_Switch
1 Bit
116
Learn object position
memory manually 1
Input
RWC-
[1.1] DPT_Switch
1 Bit
119
Automatically move to
memory position
Input
RWC-
[1.1] DPT_Switch
1 Bit
120
Learn object position
memory automatically 0
Input
RWC-
[1.1] DPT_Switch
1 Bit
121
Learn object position
memory automatically 1
Input
RWC-
[1.1] DPT_Switch
1 Bit
124
Call up / saving scenes
Input
RWC-
[18.1]
DPT_SceneControl
1 Byte