Chapter Five
Specifications
man_105_2.9.doc
Page
55
Chapter Five
SPECIFICATIONS
General
EMC approval
EN55022 (CISPR 22)
- CLASS B
EN 50082-1
ETS 300 683
AS 3548
IEC60950
89/336/EEC
Radio standards
105U only
MPT 1329 UK
EN-300-220
AS 4268.2 AUST
RFS29 NZ
458 MHz, 500 mW EIRP
430 - 450 MHz, 10 - 500 mW
869 MHz, 500mW
472 MHz, 100 mW EIRP
458 MHz, 500 mW EIRP
Housing
130 x 185 x 60mm
DIN rail mount
Powder-coated, extruded aluminium
Terminal blocks
Removable
Suitable for 2.5 mm
2
conductors
LED indication
Power supply,
OK operation, digital I/O,
RX and TX
Operating Temperature
-20 to 60 degrees C
Power Supply
Battery supply
11.3 - 15.0 VDC
AC supply
12 - 24 VAC, 50/60 Hz
Overvoltage protected
DC supply
15 - 30 VDC
Overvoltage and reverse voltage
protected
Mains supply
110-250 VAC
via plug-pack transformer
Battery Charging circuit
Included
for 1.2-12 AHr sealed lead acid
battery
Solar regulator
Included
Direct connection of solar panel (up
to 30W) and solar battery (100 AHr)
Current Drain
70 mA quiescent for ‘U’
45 mA quiescent for ‘S’
+ 10 mA/active digital input
+ 25 mA/active digital output
+ 2 x analogue I/O loop (mA)
Radio transmitter inrush
400mA @ 13.8VDC
250mA @ 24VDC
500mW RF power
Analogue loop supply
Included, except 105-4
24V DC 150 mA
Mains
fail
status
Monitored
Can be transmitted to remote
modules
Battery voltage
Monitored
As above