105 Radio/Serial Telemetry Module
User Manual
Page
72
©
January 2004
40%, DO2 at the pump station will
activate to start the pump. When the level
rises above 75%, DO2 will reset to stop
the pump.
•
The update time for SETPOINT1 has been
changed to 5 minute, as required.
•
An additional mapping has been entered -
LOW VOLT has been mapped to DO7 at
#96 via #1 (DO7 at the control station).
This mapping is for future use - it will
provide a low battery voltage alarm for the
tank station. The update time for this mapping has been set to the maximum time of 15
minutes to reduce loading of the radio channel.
•
A Start-up poll has been configured for #1, as DO1 at the tank station is controlled from
the pump station. Note that no comms fail reset time has been configured for DO1. As
this output drives an indication only, the indication will show the last correct status even
during communication failures.
Pump Station Configuration
The 105U-1 module has the following configuration :-