105 Radio/Serial Telemetry Module
User Manual
Page
48
©
January 2004
if mapped to an analogue output).
To configure the pulse rate scale, select “Pulse Inputs” on the left-hand menu and select the
“Rate” page - double-click the pulse input rate and enter the scale value.
Pulse Output Update
Time Configuration
The pulse output
update time is the time
period over which
pulses are output after
a PI update is received.
It should be configured
to correspond to the
pulse input update time
for the corresponding
pulse input. This
ensures that the pulse
output rate matches as
closely as possible the
pulse input rate which
it is reflecting.
For example, if the PI
update time is 1 minute, then the PO update time should also be 1 minute. If the PI update
time is changed, then the PO update time at the remote module should be also changed. The
PO will still operate if the time is not changed, however pulses may be output faster or
slower than the input pulses.
To configure the pulse output
time, select “Pulse Outputs”
on the left-hand menu and
select the “Pulsed Output
Time” page - double-click
the pulse output and enter the
new time.
Pulse Output Enable
The PO’s for the 105-2 and
105-4 modules are also DO1-
4. To use as pulse outputs,
you need to enable them as
pulse outputs.
To enable pulse outputs, select “Pulse Outputs” on the left-hand menu and select the
“Enable/Disable” page - double-click the pulse output to enable.