Chapter Six
Troubleshooting
man_105_2.9.doc
Page
65
successfully.
Example (105-1):
>c
Comms
01FA8106008005C6727D44
Command message transmitted by this unit.
*01FA8186C6E0E3
Corrupt Acknowledge received from remote.
01FA8106008005C6727D44
Message re-transmitted by this unit. (no Ack)
01FA818600E0E3
Valid Acknowledge received from remote.
*01FB860100800100009286
Corrupt message received from remote unit.
01FA860100800100009286
Re-sent message received from remote unit.
01FA868100FCE4
Acknowledge message from this unit to remote.
DO1 to DO8, DIO1 to DIO12
These options allow the user to set and clear digital outputs. To set an output, select the
corresponding menu item, at the prompt, type the value FFFF to turn the output ON, or 0000
to turn the output OFF. For example, to set DO1 ON,
>e
DO1
>FFFF
AO1 to AO8
These options allow the user to set analogue outputs to any value. To set the output, select the
corresponding menu item. At the prompt type the value required for the analogue output as a
four digit hexadecimal value. Refer to the table above for analogue current/expected value
relationship. To set AO2 on 105-3 to 19 mA :
>m
AO2
>B800
Switch
This option allows testing of the DIL (Dual In Line) switches. The diagram below indicates
the layout of the switches of which there are two sets of eight, with an “Enter” button located
to the right of the pair. the display indicates the current switch settings with the digit ‘1’
corresponding to ‘On’ and the digit ‘O’ corresponding to ‘Off’. Changing the switch settings
in this mode will change the display. Test each switch and check to ensure the display
changes accordingly.
Switches
Displayed
1110001001010101
1 1 1 0 0 0 1 0
0 1 0 1 0 1 0 1