105 Radio/Serial Telemetry Module
User Manual
Page
42
©
January 2004
1.
The I/O mapping display will show all inputs at the selected module - both physical
inputs and internal inputs. Select the input to be mapped.
2.
If you wish to invert the mapping, select the “Invert Input” box. If you invert an input,
then the output will be the reverse of the input. Analogue I/O can also be reversed -
0mA will be 24mA, 4mA will be 20mA etc.
Do not invert pulse inputs.
3.
The invert function is not available on 105-2 modules - only inverted digital inputs are
available (as internal inputs on the input list).
4.
To select the destination module, you can either select the module from the “Destination
Unit” list, or enter the unit address in the “To Destination” box. You can enter an
address that has not yet been allocated to another unit.
5.
You can select the output by entering the output number (1 – 255) in the “output” box, or
select an output from the displayed list. There will only be a list of possible outputs
displayed if at step 2 you selected a desrtination unit that has already been configured in
the system.
The output numbering for each module is:
105-1
105-2
105-3
First addr
(Even)
105-3
Second addr
(Odd)
105-4
First addr
(Even)
105-4
Second addr
(Odd)
Output 1
DO 1
DO 1
D/P O 1
AO 1
D/P O 1
DIO 5
Output 2
DO 2
None
D/P O 2
AO 2
D/P O 2
DIO 6
Output 3
DO 3
None
D/P O 3
AO 3
D/P O 3
DIO 7
Output 4
DO 4
None
D/P O 4
AO 4
D/P O 4
DIO 8
Output 5
AO 1
None
DO 5
AO 5
DIO 1
DIO 9
Output 6
AO 2
None
DO 6
AO 6
DIO 2
DIO 10
Output 7
PO
None
DO 7
AO 7
DIO 3
DIO 11
Output 8
None
None
DO 8
AO 8
DIO 4
DIO 12
6.
If you select a 105U-C or –G as the destination module, you will be asked to select a I/O
Register as the destination “output”. Note that the grey-shaded I/O registers have already
been allocated.
7.
Select any intermediate repeater units needed to reach the destination address (entered in
order of nearest to furthermost repeater). You can either select from the list of configured
units or enter the unit address in the “Repeater” box. If no repeaters are required, do not
enter anything in the repeater boxes. If only one repeater address is required, enter the
address in box 1 and leave the other repeater boxes empty.
It is possible to configure multiple mappings for an input - each mapping will generate
separate transmissions. We recommend that you do not configure multiple mappings to the
same output as the output will have the value of the last message that it receives. Each output
should have only one mapped input.