Chapter One
Introduction
man_105_2.9.doc
Page
7
•
The
105U-C
and
105U-G
modules provide an interface between host devices such as
PLC’s or SCADA computers, and a radio telemetry system comprising 105U and 505U
radio telemetry modules. The 105U-C and -G allows 105U/505U modules to act as
remote wireless I/O for the host devices. For more information, refer to the relevant
User
Manual.
Product naming convention:
1 0 5
a
–
x
where
a
is:
U = UHF radio + RS232/RS485 serial
S = RS232/RS485 serial only
and
x
is:
1 = Input / Output module
2 = Input module ( includes one output)
3 = Output module
4 = Input / Output module
C= Interface module
105U-1
105S-1
105U-2
105S-2
105U-3
105S-3
105U-4
105S-4
Radio
!
!
!
!
Serial
!
!
!
!
!
!
!
!
Digital
Inputs (DI)
4
4
4 to 16
Digital
Outputs (DO)
4 (relay)
1 (FET)
8 (FET)
4 to 16 (FET)
Analogue
Inputs (AI)
2 (4-20mA)
6 (0-20mA)
Analogue
Outputs (AO)
2 (4-20mA)
8 (0-20mA)
Pulse Inputs
(PI)
1 (100Hz)
4 (1x1KHz,
3x100Hz)
4 (1x1KHz,
3x100Hz)
Pulse
Outputs (PO)
1 (100Hz)
4 (100 Hz)
4 (100 Hz)
Comments
PI is DI 1. PO is
separate to DO.
PI’s are the same
as DI’s.
PO’s are the same
as DO’s .
PI/ PO’s are the
same as DI/ DO’s.
Note regarding 105-4 modules.
The 105-4 has a total of 20 digital I/O. Four are fixed
inputs (also PI’s) and four are fixed outputs (also PO’s). The other 12 are selectable
individually as DI or DO. The I/O range can vary from 16DI + 4DO to 4DI + 16DO or any
combination in between.
All modules include power supply, microprocessor controller, input/output circuits,
RS485/232 serial port, and a UHF radio transceiver - no external electronics are required.