15P0082B8
USER MANUAL
SINUS/ISD
6 - 12/82
6.4.1.4
AUTO RESTART
Auto Restart (or Auto Reset)
provides the facility to automatically
reset a choice of trip events and
restart the drive with a programmed
number of attempts, after which, a
manual or remote trip reset is
required if the drive is not
successfully restarted. The number
of attempted restarts are recorded.
This count is cleared after a trip-free
period of operation
(5 minutes or 4 x ATTEMPT DELAY
1 , whichever is the longer), or after a
successful manual or remote trip
reset. This function is inhibited in
Remote Sequencing Comms mode.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
SEQ & REF
4
AUTO RESTART
AR ENABLE
AR ATTEMPTS
AR INITIAL DLY 1
AR ATTEMPT DLY 1
AR TRIGGERS 1
AR INITIAL DLY 2
AR ATTEMPT DLY 2
AR TRIGGERS 2
AR PENDING
AR RESTARTING
AR ATTEMPTS LEFT
AR TIME LEFT
AUTO RESTART
AUTO RESTART
PENDING [608] ––FALSE
RESTARTING [616] ––FALSE
ATTEMPTS LEFT [614] ––5
TIME LEFT [615] ––10.0 s
FALSE –– [611] ENABLE
––
5 –– [612] ATTEMPTS
––
10.0 s –– [610] INITIAL DELAY 1
––
10.0 s –– [613] ATTEMPT DELAY 1
––
0000 –– [609] TRIGGERS 1
––
0.1 s –– [678] INITIAL DELAY 2
––
0.1 s –– [679] ATTEMPT DELAY 2
––
0000
–
[677] TRIGGERS 2
–
Parameter Descriptions
Parameter Descriptions
ENABLE
ENABLE
Range: FALSE / TRUE
Enables operation of the auto restart feature.
ATTEMPTS
ATTEMPTS
Range: 1 to 10
Determines the number of restarts that will be permitted before requiring an external
fault reset.
INITIAL DELAY 1
INITIAL DELAY 1
Range: 0.0 to 600.0 s
Determines the delay for the first restart attempt when the trip is included in
TRIGGERS 1 .
The delay is measured from all error conditions clearing.
ATTEMPT DELAY 1
ATTEMPT DELAY 1
Range: 0.0 to 600.0 s
Determines the delay between restart attempts for a trip included in TRIGGERS 1 .
The delay is measured from all error conditions clearing.
TRIGGERS 1
TRIGGERS 1
Range: 0000
to FFFF
Allows Auto Restart to be enabled for a selection of trip conditions.
Refer to “Hexadecimal Representation of Trips” at the beginning of this chapter for an
explanation of the four-digit code.
INITIAL DELAY 2
INITIAL DELAY 2
Range: 0.0 to 600.0 s
Determines the delay for the first restart attempt when the trip is included in
TRIGGERS 2
The delay is measured from all error conditions clearing.
ATTEMPT DELAY 2
ATTEMPT DELAY 2
Range: 0.0 to 600.0 s
Determines the delay between restart attempts for a trip included in TRIGGERS 2 .
The delay is measured from all error conditions clearing.
TRIGGERS 2
TRIGGERS 2
Range: 0000
to FFFF
Allows Auto Restart to be enabled for a selection of trip conditions.
If a trip is included in both TRIGGERS 1 and TRIGGERS 2, then the times associated
with TRIGGERS 1 will take priority.
Refer to “Hexadecimal Representation of Trips” at the beginning of this chapter for an
explanation of the four-digit code.
Содержание SINUS/ISD 200 S-0.75
Страница 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Страница 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Страница 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Страница 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Страница 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Страница 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Страница 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Страница 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Страница 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Страница 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Страница 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Страница 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Страница 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...
Страница 205: ...SINUS ISD 15P0082B8 USER MANUAL 16 9 10...