SINUS/ISD
15P0082B8
USER MANUAL
6 - 55/82
REMOTE REVERSE
REMOTE REVERSE
Range: FALSE / TRUE
For remote setpoints, setting this parameter TRUE inverts the demanded direction of
motor rotation.
REM TRIP RESET
REM TRIP RESET
Range: FALSE / TRUE
On a transition to TRUE, this input clears latched trips.
TRIP RST BY RUN
TRIP RST BY RUN
Range: FALSE / TRUE
This allows the rising edge of run command to clear latched trips.
POWER UP START
POWER UP START
Range: FALSE / TRUE
If TRUE, this allows the inverter to go directly to run mode if in remote and a run
command is present. If FALSE, a low to high transition of the run command is required.
TRIPPED
TRIPPED
Range: FALSE / TRUE
Indicates that there is a latched trip present.
RUNNING
RUNNING
Range: FALSE / TRUE
Indicates that that the inverter is in the enabled state.
JOGGING
JOGGING
Range: FALSE / TRUE
Indicates that the inverter is in the JOG mode.
STOPPING
STOPPING
Range: FALSE / TRUE
Indicates that the inverter is stopping.
OUTPUT CONTACTOR
OUTPUT CONTACTOR
Range: FALSE / TRUE
Output to be used to drive an external contactor in the motor output. This contactor is
normally closed unless a Trip condition has occurred or the inverter goes into the re-
configuration mode.
SWITCH ON ENABLE
SWITCH ON ENABLE
Range: FALSE / TRUE
Sometimes referred to as READY TO SWITCH ON, this parameter indicates that the
inverter will accept a run command.
SWITCHED ON
SWITCHED ON
Range: FALSE / TRUE
Indicates that the inverter’s power stack is operable and the inverter will run if enabled.
READY
READY
Range: FALSE / TRUE
Output indicating that the inverter has accepted the run command.
SYSTEM RESET
SYSTEM RESET
Range: FALSE / TRUE
Output TRUE for a single cycle after the inverter enters either RUN or JOG mode.
MAIN SEQ STATE
MAIN SEQ STATE
Range: Enumerated - see below
This parameter indicates the current sequencing state:
Enumerated Value
:
State
0 : NOT READY
1 : START DISABLED
2 : START ENABLED
3 : SWITCHED ON
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
REMOTE REV OUT
REMOTE REV OUT
Range: FALSE / TRUE
This parameter indicates the current state of remote direction and RUN REV. Note - this
is the demanded direction, not the actual direction.
HEALTHY
HEALTHY
Range: FALSE / TRUE
Set FALSE when the inverter trips, and set TRUE when the the run command is
removed.
Содержание SINUS/ISD 200 S-0.75
Страница 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Страница 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Страница 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Страница 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Страница 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Страница 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Страница 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Страница 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Страница 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Страница 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Страница 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Страница 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Страница 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...
Страница 205: ...SINUS ISD 15P0082B8 USER MANUAL 16 9 10...