6.4.1.1
ANALOG DIGIN
The analog digital input block allows the analog input terminals to be used as digital
input signals.
Functional Description
The SINUS/ISD inverter has two analog inputs. There is a digital analog input function block for each: ANALOG
DIGIN 1 is associated with the signal on terminal 2, whilst ANALOG DIGIN 2 is associated with the signal on
terminal 4.
The analog digital input function blocks allow the analog terminals to be used as digital inputs where extra digital
inputs are required. The input voltage or current is converted to a TRUE or FALSE digital signal. Generally,
(when INVERT is FALSE), an input greater than the comparison LEVEL
will cause the output VALUE
to be
TRUE. Similarly, an input less than the comparison LEVEL
will cause the output VALUE
to be FALSE.
+10V
-10V
0%
30%
100%
0 (FALSE)
1 (TRUE)
LEVEL
TRUE
FALSE
VALUE
raw input
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
INPUTS & OUTPUTS
4
ANALOG DIGIN
5
ANALOG DIGIN 1
5
ANALOG DIGIN 2
A DIN 2 INVERT
A DIN 2 LEVEL
A DIN 2 HYST
A DIN 2 VALUE
ANALOG DIGIN 2
ANALOG DIGIN 2
VALUE [95] – FALSE
FALSE – [94] INVERT
–
70.00 % – [96] LEVEL
–
10.00 % – [97] HYSTERISIS
–
ANALOG DIGIN 1
ANALOG DIGIN 1
VALUE [ 90] – FALSE
FALSE – [ 89] INVERT
–
70.00 % – [ 91] LEVEL
–
10.00 % – [ 92] HYSTERISIS
–
Parameter Descriptions
Parameter Descriptions
INVERT
INVERT
Range: FALSE / TRUE
When this is TRUE, the VALUE output is inverted.
LEVEL
LEVEL
Range: 0.00 to 100.00 %
This is the level used to determine whether the input is high or low. The actual level
also depends on the hardware range selected.
HYSTERISIS
HYSTERISIS
Range: 0.00 to 50.00 %
A hysteresis value used to prevent jitter on the input. The actual hysteresis also
depends on the hardware range selected.
VALUE
VALUE
Range:FALSE / TRUE
A TRUE or FALSE output depending on the input volts or current.
Содержание SINUS/ISD 200 S-0.75
Страница 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Страница 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Страница 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Страница 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Страница 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Страница 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Страница 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Страница 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Страница 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Страница 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Страница 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Страница 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Страница 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...
Страница 205: ...SINUS ISD 15P0082B8 USER MANUAL 16 9 10...