USER MANUAL
6 - 63/82
6.4.1.41
STOP
This function block holds all the
parameters concerning the stopping
method of the inverter.
The stopping methods of the inverter
are described in more detail in Chapter
4: “Operating the Inverter” - Starting and
Stopping Methods..
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
SEQ & REF
4
STOP
RUN STOP MODE
STOP RATE
STOP ZERO SPEED
STOP DELAY
FAST STOP MODE
FAST STOP LIMIT
FAST STOP RATE
FINAL STOP RATE
STOP
STOP
RAMPED – [279] RUN STOP MODE
––
10.0 s –– [263] STOP RATE
––
0.10 % –– [266] STOP ZERO SPEED ––
0.500 s –– [284] STOP DELAY
––
RAMPED –– [304] FAST STOP MODE ––
30.0 s –– [275] FAST STOP LIMIT
––
0.1 s –– [264] FAST STOP RATE
––
1200 Hz/s
–
[126] FINAL STOP RATE
–
Parameter Descriptions
Parameter Descriptions
RUN STOP MODE
RUN STOP MODE
Range: Enumerated - see below
Selects stopping mode that the controller will use once the run command has been
removed. The choices are:
Enumerated Value
:
Stopping Mode
0 : RAMPED
1 : COAST
2 : DC INJECTION
When RAMPED is selected, the inverter will decelerate using the system ramp
deceleration time, provided it is non zero. When COAST is selected, the motor will free-
wheel. When DC INJECTION is selected, the motor is stopped by applying dc current.
STOP RATE
STOP RATE
Range: 0.0 to 600.0 s
Rate at which the demand is ramped to zero after the ramp has been quenched.
STOP ZERO SPEED
STOP ZERO SPEED
Range: 0.00 to 100.00 %
Threshold for zero speed detection used by stop sequences.
STOP DELAY
STOP DELAY
Range: 0.000 to 30.000 s
Sets the time at which the inverter holds zero speed before quenching after a normal
stop or a jog stop. This may be particularly useful if a mechanical brake requires time to
operate at zero speed, or for jogging a machine to position.
FAST STOP MODE
FAST STOP MODE
Range: Enumerated - see below
Selects stopping mode used during a fast stop, two options ramped or coast.
Enumerated Value
:
Stopping Mode
0 : RAMPED
1 : COAST
FAST STOP LIMIT
FAST STOP LIMIT
Range: 0.0 to 3000.0 s
Maximum time that the inverter will try to Fast Stop, before quenching.
FAST STOP RATE
FAST STOP RATE
Range: 0.0 to 600.0 s
Rate at which the SPEED DEMAND is ramped to zero (see REFERENCE function
block)
FINAL STOP RATE
FINAL STOP RATE
Range: 12 to 4800 Hz/s
Rate at which any internally generated setpoint trims are removed. For example, the trim
due to the slip compensation block.
Содержание SINUS/ISD 200 S-0.75
Страница 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Страница 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Страница 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Страница 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Страница 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Страница 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Страница 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Страница 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Страница 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Страница 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Страница 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Страница 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Страница 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...
Страница 205: ...SINUS ISD 15P0082B8 USER MANUAL 16 9 10...