4: Electrical Installation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
4.3: Installing Current Transformer Sensors with No Meter
Termination (Pass Through)
The second method allows the CT wires to pass through the CT inputs without
terminating at the meter. In this case, remove the current gills and place the CT wire
directly through the CT opening. The opening accommodates up to 0.177"/4.5mm
maximum diameter CT wire.
Figure 4.2: Pass Through Wire Electrical Connection
NOTE:
For sustained loads greater than 10 A, use 10 AWG wire.
CT wire
passing
through
meter
with
current
gills
removed
Close-up of CT
openings